Resources & Support > FAQ > Inverters – Powering Direct / Embedded SMPS

Inverters - Powering Direct / Embedded SMPS

What is the nature of current drawn by Switch Mode Power Supplies (SMPS)?

Power supplies are used to convert AC voltages like 120 VAC to various DC voltages like 3.3 V, 5 V, 12 V, 24 V, 48 V etc. Majority of modern day electronic devices use embedded general purpose Switch Mode type of Power Supplies (SMPS) to drive the electronic circuitry. General purpose Switch Mode Power Supplies (SMPS) (excepting those that have power factor correction) have one major disadvantage – the current drawn by them from the AC power source has a non linear waveformthe waveform is not sinusoidal as the input voltage waveform but is in the form of short, larger value pulses around the area of + Vpeak and -Vpeak. This is due to the charging of the input filter capacitor(s) mostly around the positive and negative peak portions of the sinusoidal input voltage.

What is crest factor?

The degree of non-linearity is measured by the “Crest Factor“: Crest Factor = Peak Current / RMS Current

In a linear load, the Crest Factor is 1.414. However, in a general purpose SMPS, due to its non linear nature, this factor will be much higher – in the region of up to 4. This will mean that for a particular rated RMS current (applicable for a linear load), the general purpose SMPS will draw much larger peak currents – approx. up to 4 times more than its rated RMS current.

What is Power Factor?

If a linear load is connected to this type of voltage, the load will draw current which will also have the same sine wave-form. However, the peak value of the current will depend upon the impedance of the load. Also, the phase of the sine wave-form of the current drawn by the linear load may be the same or lead / lag the phase of sine wave-form of the voltage. This phas difference determines the “Power Factor (mathematically = the cosine of the phase difference)” of the load.

Why does a DC/AC inverter prematurely shut down while supplying power to a general purpose Switch Mode Power Supply (SMPS)?

For safe operation, the continuous RMS current rating of the inverter / generator should be at least 2.8 times the continuous RMS current rating of the general purpose SMPS it is required to power:

Peak current of inverter = Peak current of SMPS

or

RMS current of inverter X 1.414 = RMS current of SMPS X 4

or

RMS current of inverter = 4/1.414 X RMS current of SMPS

or

RMS current of inverter = 2.8 X RMS current of SMPS

Alternatively, the continuous power rating of the inverter / generator in Watts / VA should be at least 2.8 times the continuous power rating of the SMPS in Watts / VA